|
|
Application Notes-306 |
|
3250 Series AC & DC Electronic Loads - Application Description |
|
The 3250 Series consists of part numbers 3250 (60V/20A/300W), 3251 (150V/8A/300W), and 3252 (300V/4A/300W). These AC & DC electronic loads are suitable for endless DC, AC, or DC and AC power source testing purposes; for example, testing AC to DC power supplies, AC to DC voltage adapters, DC to DC power supplies, AC transformers, Intercom System ring generators. (See figures 1 through 5) This article will discuss AC operation, DC operation and other functions in detail. | |
Figure 1 Example of AC & DC Power Supply TestingFigure 2 Example of DC & DC converter testing |
|
|
Figure 3 Example of DC & AC Inverter testing |
|
Figure 4 Example of Power Transformer testing |
|
|
Figure 5 Example of Power Transformer and Rectifier testing | |
|
|
|
1. AC
Operation
1.1 Constant Current
Operation Mode
|
|
|
Figure 6 AC Equivalent circuit of CC mode operation | |
1.1.2 The constant current mode may be used for AC source load adjustment or source capacitance testing. These functions may be programmed via the GPIB, RS-232C interface. 1.1.3 With a constant current, the loads needs to be set to match the input AC source frequency in order to assure load current and voltage are in the same phase. The 3250 series loads have the capability of detecting zero crossing and input load wave form. There are five different Crest Factor (peak value) current wave forms suitable for testing input voltage peak current capability: 1.414, 2, 2.5, 3.0, and 3.5. Please see the following block diagram. |
|
1.1.2 The constant current mode may be used for AC source load adjustment or source capacitance testing. These functions may be programmed via the GPIB, RS-232C interface. 1.1.3 With a constant current, the loads needs to be set to match the input AC source frequency in order to assure load current and voltage are in the same phase. The 3250 series loads have the capability of detecting zero crossing and input load wave form. There are five different Crest Factor (peak value) current wave forms suitable for testing input voltage peak current capability: 1.414, 2, 2.5, 3.0, and 3.5. Please see the following block diagram. |
|
Figure 7 Block diagram of CC mode operation
1.2 Constant Resistant Operation Mode
|
|
Figure 8 AC Equivalent circuit of CR mode operation | |
1.2.2 The constant resistance operation mode may be used for over current start testing or AC power start up. While it can also be used for testing load adjustment rates or power capacity the power source output voltage will decrease as the current increases. Voltage and current should be recorded at the same time in order to calculate the change rate, which is different from the constant current mode previously discussed as having a stable load current where it is only necessary to record the voltage for the change rate. 1.2.3 There is no need to set these units in the constant current mode because the electronic load current wave form reference source is a voltage wave form. (Please see diagram below) |
|
Figure 9 Block diagram of CR mode operation | |
2. DC Operation
2.1 Constant Current Mode
|
|
Figure 10 DC Equivalent circuit of CC mode operation | |
2.2
Constant Resistant Mode
Refer to 1.2.1 substituting 'DC source' for 'AC source'. Please refer to figure 11. |
|
Figure 11 DC Equivalent circuit of CR mode operation | |
3. Other Operation Features
3.1 Electronic Meter
|
|
Figure 12 Function diagram of Electronic Meter | |
3.2 GO/NG Comparison
This series has upper limit and lower limit measurement comparison function capability. When the measured value is between upper and lower limits it is a GO or pass. Outside these limits the reading is a NG or fail and the NG L.E.D. will light up to indicate there is a failing condition. Measuring values include voltage, current, watt and VA; each has its own upper and lower limit and all values must be within the proper limits for the tested unit to pass. This series' displays only show an NG L.E.D. When using logic symbols, results will be as follows: |
|
When using a block diagram, the NG function will appear as follows: | |
Figure 13 Block diagram of GO/NG function | |
3.3 Load ON/OFF
3.4 V Sense ON/OFF
3.5 Setting for Constant
Current Operation Mode
3.5.1 Frequency
3.5.2 Wave Form Bank
If the preset wave forms in the constant current or the constant resistance modes do not meet specified requirements, unique wave forms had been created. Refer to the 3250 Series Operation Manual for more Crest Factor, Square, and Step wave forms.
3.5.3 Synchronize Signal
Source
This series has an internal self synchronizing mode. When set in the SYNC Off position, the internal zero crossing sensor will recognize a wave form zero crossing signal and convert it to a square wave. This signals the internal wave form generator to force synchronization. As a result, load current wave form is related to voltage wave form. If the voltage wave form is incorrect, this internal synchronization will not occur. In this case, external synchronization should be used otherwise only constant resistance can be used to synchronize load current and voltage wave forms. User should provide a square wave that synchronizes with the voltage to the mainframe BNC input, and set module SYNC to On in order for the constant wave form generator to synchronize with the external signal source. 4. Making A Selection 4.1 Selecting A Load Module The 3250 Series consists of part numbers 3250 (60V/20A/300W), 3251 (150V/8A/300W), and 3252 (300V/4A/300W). Select the load that meets your voltage and current requirements. Higher accuracy is achieved when the module selected has a current rating closest to the application. If the power rating exceeds the power of a single module it is possible to parallel additional modules to achieve the power requirements. 4.2 Selecting a 3300 Series Mainframe 4.2.1 When a single module will satisfy the testing requirements, the 3302 electronic load mainframe would be the best choice. If requirements are expected to expand, a 3300A should be considered as up to three additional modules may be added as required. Blank panels may be purchased in the interim. Both the 3302 and 3300A can be purchased with or without a GPIB interface. 4.2.2 The 3300A mainframe accepts up to four 3310 and/or 3250 electronic load modules, in any combination. For a multi or mixed load requirement this is the best choice. 4.2.3 The 3300A and 3302 mainframes can be paralleled. There is no limit on the number of mainframes/modules that can be connected in parallel. |
|