|
|
Application Notes-700 |
|
|
|
|
|
Using 7550
Precision Current Shunt
|
|
|
|
2. Current meter calibration For a very stable but not precision enough current source, the current source, current meter and current shunt should be put in series. The reading on the current shunt acts as a standard reading. The calibration procedure is as follows: a. Select the appropriate current shunt range by S1 to S5. b. Program current source output until the current reads the rated testing current. c. Adjust the current meter (U.U.T to be calibrated) until its reading is same as the current shunt's reading. d. Repeat procedure a- c for different range, if required. |
|
|
|
|
3. Current sensor
calibration For a very stable but not precise enough current source, the current source, current sensor and current shunt should be put in series. The reading on the current shunt acts as a standard reading. The calibration procedure is as follows: a. Select the appropriate current shunt range by S1 to S5. b. Program current source output until the current reading on current shunt is the rated testing current. c. Adjust the current sensor (U.U.T to be calibrated) until its reading is the same as the current shunt's reading. d. Repeat procedure a - c for different range, if required. |
|
|
4. Power supply output
current calibration In the CC mode the Current shunt can be used to verify a Power Supply's output current stability and to calibrate its current meter. Test procedure is described below: a. Select the appropriate current shunt range. b. Program the CC output current from zero to the rated testing current. c. Verify the current output stability of the Power Supply by comparing the reading deviation of the shunt's current reading. d. Calibrate and adjust the Power Supply's current meter to the shunt's current reading. e. Repeat procedure a - d for different range, if required. |
|
5. Electronic load's current
meter calibration Normally, the current source output compliance voltage is less than 3V (even lower than 1V), limiting its output VA capacity. While it may be no problem to calibrate a current meter or current sensor with a very low input impedance, it is a problem to calibrate an Electronic Load with normal operating voltage of more than 3V. The current source can not supply its output current on such compliance voltage. To solve the compliance voltage problems on the current source, the following connection diagram uses an Electronic Load and Current Shunt to replace a current source. The Current shunt can be used to verify the output current's stability of an Electronic load in CC mode and to calibrate its current meter. Test procedure is described below: a. Select the appropriate current shunt range by S1 to S5. b. Program the Electronic load's CC (Constant Current) output current from zero to the rated testing current. Adjust the Power supply's output voltage higher than the minimum operating voltage on the Electronic Load to be calibrated (U.U.T). c. Verify the current output stability of Electronic Load by comparing the reading deviation of the shunt's current reading. d. Calibrate and adjust the Electronic Load's current meter to the shunt's current reading. e. Repeat procedures a - d for different range, if required. |
|